Alarm and limiting with variable limits 148, Allv 148 – West Control Solutions KS98-1 User Manual

Page 148

Advertising
background image

III-8.2

ALLV ( alarm and limiting with variable limits (No. 41))

Signal limiting:

Analog input H1determines the maximum limiting,

L1 determines the minimum limiting. y1 is limited to the range

between

L1 and H1 (L1 ß y1 ß H1).

As both

H1 and L1 come from analog inputs, H1 can be smaller than L1. In this case, H1 is assigned a higher pri-

ority. This means that signal

y1 is ß H1!

Limit signaller:

The limit signaller has 2 low and high alarms (

L1, L2, H1 and H2). The variable to be monitored can be se-

lected with configuration parameter Select (

x1, dx1/dt, x1 - x0).

The limit values are freely adjustable via the analog inputs

H1 and L1 and have an adjustable hysteresis of ? 0.

The smallest separation between a minimum and a maximum limit value is 0. With an alarm triggered, the relevant
output (

L1, L2, H1 and H2) is logic “1".

D alarm (

dx1/dt)

Value x1(t-1) measured one sampling interval before is subtracted from instantaneous value x1(t). This difference is di -
vided by calculation cycle time Tr (100, 200, 400, 800ms).

Thus input variable x1 can be monitored for rate of change.

9499-040-82711

Limit value signalling and limiting

ALLV ( alarm and limiting with variable limits (No. 41))

III-148

Select

H2

L2

Y1
h1
h2
l1
l2

Xsd

X0

X1

H1
L1

_

H2

L1

H1

Fig. 12 Limiting at H1 < L1