RM_AO (RM200 - analog output module (No. 18))

Function

RM_AO handles the data from connected analog output modules.

Input and outputs

Analog inputs

Slotx

Connection of one of the

Slot outputs of the RM 200 node (C_RM2x)

AO 1...AO 4 1st to 4th analog output signal

Digital outputs

et-err

0 = no engineering error detected

1 = engineering error (several RM module functions on a slot)

slotId

0 = correct slot assignment

1 = faulty slot assignment (wrong RM module fitted)

valid

0 = no data

1 = data could be received

fail 1

...

fail 4

Measurement error on channel 1 to 4 (e.g. sensor break)

Parameter and configuration data

Configuration

Description

Range

Default

MTyp

Module type

0: RM231-0 = 4 x 0/4...20 mA / 4 x 0...10 V
1: RM231-1 = 4 x 0/4...20 mA / 2 x 0...10 V / 2 x -10...10 V
2: RM231-2 = 4 x 0/4...20 mA / 4 x -10...10 V

OTyp 1

...

OTyp 4

Output signal

10: standard signal = 0 ... 10V
11: standard signal = -10 ... 10V
20: standard signal = 0 ... 20 mA
21: standard signal = 4 ... 20 mA

x0 1

Scaling start value input 1...input 4

-29 999 ... 999 999

0

...

x0 4

x100 1

Scaling end value input 1 ... input 4

-29 999 ... 999 999

100

...

x100 4

I/O extensions with CANopen

9499-040-82711

III-180