Analog output card (i_out) 307, Out a, Out b – West Control Solutions KS98-1 User Manual

Page 307

Advertising
background image

III-20.5

I_OUT (analog output card 0/4...20mA, +/-20mA)

Analog output, plugs into modular options card C. The I_OUT is used for configuration and parameter setting of analog
output

I_OUT. Output calculation is fixed to once per time slot.

Digital output:

slotid

0 = correct module fitted
1 = wrong module fitted

Analog inputs:
X_a

output value for channel a

X_b

output value for channel b

Configuration

Description

Values

Default

Typ_a

0...20mA

0

0

4...20mA

1

+/-20mA

2

x0_a

Physical value Inp_a at 0%

Real

0

x100_a

Physical value Inp_a at 100%

Real

100

Typ_b

0...20mA

0

0

4...20mA

1

+/-20mA

2

x0_b

Physical value Inp_b at 0%

Real

0

x100_b

Physical value Inp_b at 100%

Real

100

Modular I/O - extension-modules

9499-040-82711

III-307

I_OUT (analog output card 0/4...20mA, +/-20mA)

HARDW

ARE

SOFTW

ARE

+/-20mA
0..20mA
4...20mA

OUT a

slotid

x0_a

x100_a

Typ_a

+/-20mA
0..20mA
4...20mA

OUT b

x0_b

x100_b

Typ_b

Advertising