Bus interface, Electromagnetic compatibility – West Control Solutions KS98-1 User Manual

Page 17

Advertising
background image

Behaviour after power failure

Storage in non-volatile EEPROM for structure, configuration, pa-
rameter setting and adjusted setpoints.

Storage in a capacitor-buffered RAM (typ. > 15 minutes) for data
of time functions (programmers, integrators, counters, ...)

Real-time clock(Option B, RS 422)

Buffer capacitor provides back-up for at least 2 days (typical).

Bus interface (

Option B)

TTL and RS422 / 485-interface

Galvanically isolated, choice of TTL or

RS 422/485 operation.

Number of multi function unitsper bus:

With RS 422/485: 99

With TTL signals: 32 interface modules (9404 429 980x1). Address
range ((00...99)See Documentation 9499-040-82911) .

PROFIBUS-DP interface

According to EN 50 170, Vol. 2.

Reading and writing of all process data, parameters, and configu-
ration data.

Transmission speeds and cable lengths
automatic transm. speed detection, 9,6 kbit/s ...12 Mbit/s

Addresses
0...126 (factory setting: 126).Remote addressing is possible.

Other functions
Sync and Freeze

Terminating resistors
Internally selectable with wire-hook switches.

Cable
According to EN 50 170, Vol. 2 (DIN 19 245T3).

Required accessories
Engineering Set PROFIBUS-DP, consisting of:

w

GSD file, Type file

w

PROFIBUS manual (9499-040-82911)

w

Function block(s) for Simatic S5/S7

Electromagnetic compatibility

Complies with EN 50 081-2 and EN 50 082-2.

Electrostatic discharge

Test to IEC 801-2,

8 kV air discharge

4 kV contact discharge

High-frequency interference

Test to ENV 50 140 (IEC 801-3)

80...1,000 MHz, 10 V/m

Effect:

£ 1%

HF interference on leads

Test to ENV 50141 (IEC 801-6)

0.15...80 MHz, 10 V

Effect:

£ 1%

Fast pulse trains (burst)

Test to IEC 801-4

2 kV applied to leads for supply voltage, and signal leads.
Effect:

£ 5%resp. restart

High-energy single pulses (surge)

Test to IEC 801-5

1 kV symmetric or 2 kV asymmetric on leads for supply voltage.

0.5 kV symmetric or 1 kV asymmetric on signal leads.

9499-040-82711

Technical data

I-17