Inputs/outputs

Digital inputs (DPROG):
hide

Display suppression (with

hide = 1 the page is not displayed in the operation).

lock

Adjustment blocking (with

lock = 1 the values are not adjustable by means of keys ID).

run

Program stop/run ( 0 = stop, 1 = run )

reset has highest priority

reset

Program continue/reset (0 = continue, 1 = reset )

preset

Program preset ( 1 = preset )

search

Start programm search run (1 = search )

p-show

Program editing enabled

halt

Program interruption (e.g. due to an exceeded bandwidth detected outside the programmer).

0 = program not halted
1 = program halted

manfree

Manual mode disabled

0 = switchover to manual mode not permitted
1 = switchover to manual mode is permitted

Digital outputs (DPROG):
run

Status program stop/run (0 = program stop ; 1 = program run)

reset

Status program reset (1 = program reset)

end

Status program end (1 = program end reached)

fkey

Status H key / interface function `fkey’ (:pressing key H causes switch-over (0 or 1))

do1... do6

status of control outputs in the actual segment

preset

This output indicates a programmer preset operation. With a single preset command, a pulse is output for
the duration of one cycle (dependent on the time slot in which the programmer is classified). If the program-
mer is held in preset continuously, this output is always active.

0 = no preset status
1 = APROG stands in preset status

manual

This output indicates the progrmmer manual mode.

0 = APROG works in automatic mode
1 = APROG works in manual mode

Analog inputs (DPROG):
PSet

Preset value for program

DBlock

Block number of 1st data function `APROGD’

ProgNo

Required program number (recipe)

SlavNo

SlavNo: Block number of a connected slave block (for coupling master and slave blocks (APROG or DPROG)

Analog inputs (DPROGD):
DBlock

Block number of cascadable data function `DPROGD’

Analog outputs (DPROG):
TNetto

Net program time ( ] Trun)

TBrutt

Gross program time (] Trun + ] Tstop)

TRest

Programmer rest time

SegNo

Actual segment number

ProgNo

Actual program number (recipe)

SegRest

Remaining segment time

Bl-no

Own block-number (e.g. for coupling master and slave blocks)

Analog outputs (DPROGD):
DBlock

Own block number

Parameter and configuration data

Parameter
DPROG

Description

Range

Default

PMode

Preset Mode:

Preset to segment

Pres.time

t

Preset to time

Pres.seg.

RecMax

Max.recipees

1..99

99

D0

Status of control outputs 6...1 with reset

0 / 1 per output

000000

Programmer

9499-040-82711

III-220

DPROG ( digital programmer (No. 27)) / DPROGD ( DPROG data(No. 28))