Inputs/outputs for CONTR and CONTR+

Digital inputs:

hide

Display suppression (with hide = 1 the operating page is not displayed).

lock

Adjustment locking (with lock = 1 the values are not adjustable by means of keys ID).

inc

Increment for manual adjustment

dec

Decrement for manual adjustment

x f

Sensor error x1...x3

yp f

Sensor error Yp

a/m

0 = automatic 1 = manual

w/w2

0 = int./ext. 1 = W2

we/wi

0 = external 1 = internal

pi/p

0 = PI action;

1 = P action 1) (r page PI/P switch-over) (not applicable to PIDMA)

d ovc+

1 = override control + with 3-point stepping controller (r page ff) (not applicable to PIDMA)

d ovc-

1 = override control - with 3-point stepping controller( r page ff) (not applicable to PIDMA)

track

0 = tracking function off; 1 = tracking function on(r page , , )

y/y2

0 = output value Y1 = output value Y2

off

0 = controller switched on 1 = controller switched off

sm/hm

0 = soft manual 1 = hard manual

ostart

1 = self-tuning start r page

w stop

1 = effective freeze

gr off

1 = gradient suppression

rstart

1 = Start the ramp r the makes a step change towards the process value and goes to the adjusted process
value according to GRW+ (GRW-). The rising flank (0r1) is evaluated.

o-hide

1 = self-tuning page display suppression

oplock

Blockage of key H (with oplock = 1, switchover to manual by means of key H is not possible).

Digital outputs:

y1

Status of switching output Y1; 0 = off 1 = on

y2

Status of switching output Y2; 0 = off 1 = on

c fail

1 = controller in error handling

off

0 = controller switched off 1 = controller switched on

a/m

0 = automatic 1 = manual

y/y2

0 = output value Y 1 = output value Y2

we/wi

0 = external 1 = internal

pi/p

feedback/integrator 0 = with 1 = without (not applicable to PIDMA)

o run

Self-tuning running

o stab

Process at rest (for self-tuning) (not applicable to PIDMA)

o err

Error during self-tuning

xw sup

Alarm suppression with change

Analog inputs:

x1

Main variable x1

x2

Auxiliary variable x2

e.g. for ratio control

x3

Auxiliary variable x3

e.g. for 3-element control

Wext

External

OVC+

Override control + r page

OVC-

Override control - r page

Yp

Position feedback

Yhm

Output with hard manual

Yadd

Feed-forward control

ParNo

Only with CONTR+; required parameter set

Casc

Cascade input for controller cascade

9499-040-82711

Controller

CONTR+ (Controllerfunction with six parametersets (No. 91))