Three-point stepping controller 236, Xtpuls xp tm, Ч ч 2 01 – West Control Solutions KS98-1 User Manual

Page 236: Xxp tpuls tm, Y1â y2â

Advertising
background image

Three-point stepping controller

Switching controller for control of a valve (e.g. temperature control by means of motorized valve and gas-air mixture)

1. Open valve;

r outputs Y1 = 1, Y2 = 0

2. Don’t move valve; r outputs Y1 = 0, Y2 = 0
3. Close valve;

r outputs Y1 = 0, Y2 = 1

To validate the adjusted X

p1

for the actuator response time, response time T

m

must be adjusted. The smallest positio-

ning step is 100ms.

+

With PMA controllers the position feedback has no influence on the PID-behaviour!

Adjusting the neutral zone
Neutral zone X

sh

can be increased in case of excessive output switching. However, note that an increase the neutral

zone will reduce the control sensitivity.
For this reason, we recommend optimizing switching frequency (actuator wear) and control sensitivity.

Three-point stepping controllers can be operated with or without position feedback Yp .

Schritt

3-point stepping controller

SchrittYP

3-point stepping controller with position feedback

whereby

Yp is not used for control. The static characteristic of a three-point stepping controller is shown in the figure

above.

The hysteresis shown in this diagram is practically unimportant, but can be calculated from the adjustable min. pulse
length T

puls

? 100ms.

X

Tpuls

Xp

Tm

sh

=

Ч Ч

2

01

,

g

With

Tpuls switched off, the shortest positioning step Tpuls is dependent of Tm, Xsh and Xp.

By varying

Xsh , a required min. pulse length Tpuls can be realized:

X

Xp

Tpuls

Tm

sh

=

Ч Ч

-

12 5

0 75

,

'

,

Controller

9499-040-82711

III-236

Control behaviour

Output Y1 (open)

Output Y2 (close)

Process value

Process value

Setpoint

Setpoint

100%

0%

100%

0%

Y1Â

Y2Â

Xn100

Xn0

W0

Weff

W100

Xeff

Xp1

Xsh

Fig.: 58
Static operating principle
of a three-point stepping
controller

Advertising