Configuration Effective controller parameters of a continuous controller

CFunc =
continuous

SplitRange

Popt

Parameter set for self-tuning (only with

CONTR+)

1...6

W0

1)

Lower limit for Weff

-29 999 ...999 999

W100

1)

Upper limit for Weff

-29 999 ...999 999

W2

1)

Additional

-29 999 ...999 999

Grw+

2)

gradient plus

off / 0,001 ... 999 999

Grw-

2)

gradient minus

off / 0,001 ... 999 999

Grw2

2)

gradient for W2

off / 0,001 ... 999 999

N0

Zero offset (effective only with CType=ratio controller)

-29 999 ...999 999

a

Factor a (effective only with CType=3-element control)

-9,99 ... 99,99

Xsh1

3)

Neutral zone (Xw > 0)

0,0 … 1000 [%]

Xsh2

3)

Neutral zone (Xw < 0)

0,0 … 1000 [%]

Y2

Additional positioning value

0 … 100 [%]

Ymin

Min. output limiting

(-100) 0 … 100 [%]

Ymax

Max. output limiting

(-100) 0 … 100 [%]

Y0

Correcting variable working point (start-up correcting variable)

-100...100 [%]

YOptm

Positioning value during process at rest (not with PIDMA)

0...100 [%]

dYopt

Self-tuning step height

5...100 [%]

Xp1(1...6)

3) 4)

Proportional band 1

0,1 … 999,9 [%]

Xp2(1...6)

3) 4)

Proportional band 2 (only with continuous controller split range)

0,1 … 999,9 [%]

Tn1(1...6)

4)

Integral action time

0 … 999 999 [s]

Tv1(1...6)

4)

Derivative action time

0 … 999 999 [s]

Titel

Title of controller page (only display)

16 characters

Einh.X

Process value unit (only display)

6 characters

W int

1)

Internal after transmission of the engineering to KS 98-1

-29 999 ...999 999

A/H

Controller status after transmission of the engineering to KS 98-1

0 or 1

1) The values must be specified in the process value unit, e.g. [°C, °F, bar, %, etc.]
2) The rate of change must be specified in units/minute e.g. °C/min). r see gradient control page 261.
3) % specifications are related to measuring range

Xn100 - Xn0 . There is no relationship to values W0 and W100.

4)

(

1...6) refers to the six parameter sets of CONTR+ (e.g. Xp1, Xp2, Xp3...Xp6).