III-18 Outputs

III-18.1

OUT1 and OUT2 ( process outputs 1 and 2 (No. 116, 117))

Functions OUT1 and OUT2 are used for process output OUT1 and OUT2 configuration and parameter setting. Depend-
ent of hardware, the outputs can be analog or relay outputs. Function OUT1 is firmly allocated to block number 81,
function OUT2 is firmly allocated to block number 82. They are calculated invariably in each time slot.

With digital input

d1 used as signal source, it is switched to the digital output as specified in Mode on an instru-

ment with relay output. With continuous output, switch-over is between 0 and 20 mA as with a logic output.

Analog input

x1 used as signal source is taken to the continuous output linearly between x0 and x100 dependent

of configuration. With switching output (relay or logic), switching from

x0 to x100 is from 50% (hysteresis = 1%).

Inputs / outputs

Digital input:

d1

Input signal with digital signal conversion

Analog input:

x1

Input signal with analog signal conversion

Configuration parameters:

Parameter

Description

Values

Default

Src

Signal source

Digital input

d1

Digital

t

Analog input

x1

Analog

Mode

Signal source action

direct/normally open

direct

t

inverse/normally closed

inverse

Type

Function of the continuous output

logic 0/20 mA

logic

0...20mA

0...20mA

t

4...20mA

4...20mA

x0

Analog input value

x1 at 0%

-29 999 ... 999 999

0

x100

Analog input value

x1 at 100%

-29 999 ... 999 999

100

9499-040-82711

Outputs

OUT1 and OUT2 ( process outputs 1 and 2 (No. 116, 117))

III-286

HARDW

ARE

SOFTW

ARE

Relais

Logik
0..20mA
4...20mA

d1
x1

OUT1
OUT2

OUT1
OUT2

Src

x0

x100

Type

Mode