System information – Setra System SRCM User Manual

Page 28

Advertising
background image

28

Zero Adjust

Pressing Zero Adjust button will bring up a “Is zero pressure

applied?” message. If yes, press OK. If the zero measure-

ment is within 10% of the factory zero measurement stored

in the unit, the zero value will be reset. Note: Zero Adjust

should only be performed after the unit has been operating

for 30 minutes in the installed location.

Span Adjust

This requires the use of a Pressure Calibrator, such as a Setra

Model 869 or equivalent. Connect tubing from the Cali-

brator to the low and high ports identified near the PCBA

markings. Apply Full Range pressure, for example ± 0.1”

WC range, use 0.1” WC. When pressure reaches Full Range

pressure, press OK button. The output at Full Range must be

within 10% of the factory calibration to allow re-adjustment.

Restore Factory User

Zero and User Span

If the unit has been miscalibrated in the field, the factory

zero and span settings can be restored.

Test

The Buzzer, Relay and Internal Memory checksum can be

tested and verified.

The System Information screen reports Model Number, Serial Number,

Firmware Revision, Network Status, Last (Factory) Calibration Date and

Technical Support Contact.

Technical Support

Any string 30 characters or shorter

can be entered in this field by press-

ing anywhere in the white text entry

box to enable the pop-up keyboard.

Enter an email address, name, or

phone number as needed.

Restore Factory Default

Restores the default settings for all con-

figuration and setup screens. All configured

settings, including alarm thresholds and

audible alarming, that were modified after

installation will be lost if this function is

used. Primary and Secondary Room Labels

will show “???.” Normal operation of pres-

sure measurement will not be affected.

System Information