Output menu, Control menu, Pid output type – Athena Technologies 16C User Manual

Page 22

Advertising
background image

19

18

Output Menu

Output 1 Action

Reverse-acting (Heating)

Direct-acting (Cooling)

Output 1 Cycle Time* 0.2; 1 to 120 seconds
Output 1 Low Limit 1-100%
Output 1 High Limit 1-100%

Output 2 Action

Reverse-acting (Heating)

Direct-acting (Cooling)

Output 2 Cycle Time* 0.2; 1 to 120 seconds
Output 2 Low Limit 1-100%
Output 2 High Limit 1-100%

*Recommended Cycle Time Settings

Output Type Recommended Setting (seconds)
B (5A/3A) 15 to 120
E (0-20 mA) 0.2
F (4-20 mA) MUST be set to 0.2
G (4-20 mA) MUST be set 0.2
S (pulsed 20 Vdc) 0.2
T (S.S. relay) 15 to 120**
Y (5A/3A) N.C. 15 to 120 (Output 2 only)

** “T” outputs directly driving non-inductive loads (small heaters) can have

cycle times as low as 0.2 seconds.

PID Output Type

Control Menu

As with the Output Menu, the Control Menu will change, depending
upon the Output Type selected.

Note: These parameters are auto-

matically set during the autotune procedure. We do not recommend
altering the value of these control parameters unless your process
requires manual tuning.

Setting Derivative

(Rate) or Integral

(Reset) to

disables that aspect

of PID control.

If BOTH outputs are

set to direct-acting or

BOTH outputs are set

to reverse-acting, then

only one proportional

band selection will be

displayed.

Display Parameter Selection

Proportional Band 1 1...to span of sensor

Proportional Band 2 1...to span of sensor

Derivative Action (Rate) 0 to 2400 seconds

Manual Reset OFF, -100% to 100%

NOTE: The Integral Action (Auto Reset) parameter appears only if OFF
is selected in the Manual Reset parameter.

Integral Action (Auto Reset) 0 to 9600 seconds

PID Output Type