Recalibration procedures, Rtd calibration values – Athena Technologies 16C User Manual

Page 37

Advertising
background image

32

33

The Series C controller

is precalibrated at the

factory. Under normal

circumstances, the

factory calibration

should be valid for the

life of the instrument.

If recalibration should

be required, allow the

controller to warm up

for 15 minutes and

follow these steps

carefully.

Recalibration

Procedures

1) Remove power from the controller and disconnect all

output devices. Disconnect input. Attach an appropriate

calibrator to the input terminals.

2) Apply power to the calibrator, making sure that the dis-

played value is not outside the range of the controller.

Then, apply power to the controller.

3) Index to the Calibration Low menu item in the Calibration

Menu.

(You must have Security Level set to “Factory” to access this menu.)

4) Dial Calibrator to prompted value on the controller’s dis-

play. See chart below for RTD resistance vs. temperature

values.

5) Allow the controller to settle for at least one minute.
6) Press Raise

Key.

7) Repeat Steps 4, 5, and 6 for the Calibration High setting.
8) Press the Menu Access key for three seconds to return to

the Process Value display.

RTD Calibration Values

RTD

Cal Lo

0° C

32° F

100

RTD

Cal Hi

768° C

1414° F

366

RT.D

Mid-range

328° C

622.4° F

222