Recipe (ramp/ soak) menu, Supervisor menu – Athena Technologies 16C User Manual

Page 28

Advertising
background image

25

24

NOTE: The following seven parameters are only available when
multi-step ramp is selected.

Display Parameter Selection

Recycle Number 0-99,

(Recipe Executions)

Power Fail Resume

Off

On

Ramp Times 1-8 0-9999 mins.
Ramp Events 1-8

Alarm 1 On

Alarm 1 Off

Alarm 2 On

Alarm 2 Off

Disabled

Soak Levels 1-8 Display Units, FS
Soak Times 1-8 0-9999 mins.
Soak Events 1-8

Alarm 1 On

Alarm 1 Off

Alarm 2 On

Alarm 2 Off

Disabled

Recipe (Ramp/

Soak) Menu

For Ramp Events and

Soak Events to be

employed, Alarm 1 or

Alarm 2 must be set for

event usage

in the

Alarm Menu.

Supervisor Menu

Display Parameter Selection

Output 1 0 to 100%

Failsafe State of output

Output 2 0 to 100%

Failsafe State of output

Loop Break Time Off, 4-9600 sec
Highest Reading n/a
Lowest Reading n/a
Load Default

Parameters

Choosing “Yes” to Load Default Parameters resets all menu

parameters to factory settings.

The Failsafe State is

only enforced when

a problem is detected

with the process

input. It is not reli-

ably enforceable in

instances of internal

circuitry failure such as

EEPROM problems.

Output % High Limits

are ignored when the

unit enters a Failsafe

State.