Wiring – Athena Technologies 16C User Manual

Page 8

Advertising
background image

4

Wiring

Figure 5. Thermocouple Input Wiring
Make sure that you are using

the appropriate thermocouple

and extension wire. Connect the

negative lead (generally colored

red in ISA-type thermocouples)

to contact #9; connect the

positive lead to contact #10.

Extension wires must be the

same polarity as the thermo-

couple.

Figure 6. RTD Wiring
The Series C accepts input from

2- or 3-wire, 100 ohm platinum

resistance temperature detectors

(RTDs). Connect 2-wire RTDs

to contacts #9 and #10, with a

jumper across contacts #8 and

#10. Keep leads short and use

heavy gauge copper extension

wire, if necessary, to minimize

lead resistance. For long runs,

3-wire RTDs should be used.

Thermocouple circuit

resistance should not

exceed 100 ohms for

rated accuracy; errors

will occur at higher

resistance values.

If shielded thermo-

couple wire is used,

terminate the shield

only at one end.

8

9

10

RTD

8

9

10

T/C

Note: For 2-Wire RTD

Jumper 8 & 10

Wiring

Figure 7. Process and Linear Input Wiring
Voltage Inputs
: Connect the positive

voltage input to contact #10; the

negative input to contact #9.

Current Inputs: Connect the positive

current input to contact #10; the

negative input to contact #9.

The Series C power supply accepts

100 to 250 Vac and 100

to 250 Vdc line power without any switch settings or

polarity considerations. All connections should be made

in accordance with the National Electrical Code and local

regulations, using only NEC Class 1 wiring for all power

terminals.
It is advisable, but not necessary, to fuse one leg of the

incoming power line, contact #11, with a 2AG, 0.5 amp

rated fuse. It is recommended that instrument power and load

power be fused independently.
Figure 8. Power Wiring Connection

3

4

5

8

9

10

11

12

L1 L2

100 - 250 V 50/60 Hz
100 - 250 Vdc (Auto Polarity)

Advertising