23

Recipe (Ramp/

Soak) Menu

Power Fail Resume

Setting this parameter to On will cause the control to resume

a recipe which was active when a power failure occurred. The

recipe will resume at the start of the last active ramp or soak

segment.

Ramp/Soak Events (1-8)

(If alarms are configured as ramp/soak events.)

Ramp/Soak events occur at the beginning of their designated

segment. All events are terminated once the recipe has been

completed or terminated. This can be used as an alarm when a

segment is reached.

Display Parameter Selection

Recipe Option

Single-Setpoint

Ramp

Multi-Step Ramp

Disabled

Single-Setpoint 1-9999 mins.

Ramp Time*
*NOTE: Only available when single-setpoint ramp is selected.

Holdback Band Off-100 degrees
Termination State

Last Setpoint

Default Setpoint

Recipe to Standby

If a ramp/soak error

condition occurs, the

upper display will

toggle between

and the numeric error

code for three seconds

before the recipe

terminates. Possible

error codes are:

02 = Recipe Empty

(i.e. no non-zero ramp

times)

05 = Insufficient

Setpoint-Process Value

Deviation