Glossary – Athena Technologies 16C User Manual

Page 44

Advertising
background image

40

41

input failure, or a heater or load failure.

Loop Break Time

- the time interval from when the controller detects a

loop break condition and the initiation of the failsafe state.

Lowest Reading

- records the lowest process value read by the controller.

May be reset to zero by using the Raise or Lower arrow keys.

Lower Setpoint Limit

- prohibits users from adjusting the setpoint lower

than the selected value.

Manual Reset

- an adjustment that moves the Proportional Band up or

down by a fixed percentage so that more or less power is applied at set-
point. It is used to eliminate offset error.

On/Off Output Type

- In a heating application, the controller applies 100%

output power if the process temperature is below the setpoint and 0% at
the setpoint. For a cooling application, the controller applies 100% output
power if the process temperature is above the setpoint and 0% output
power at the setpoint. There are only two output states: fully on and fully
off.

Applications for On/Off Control:

1. When temperature oscillation is acceptable.

2. When constant cycling of mechanical devices is

prohibited (Compressors, Blowers, etc.)

3. Under-powered processes

Output Low Limit %

- Prohibits the controller’s output from going

below the specified percentage.

Output High Limit %

- Prohibits the controller’s output from going above

the specified percentage.

PID Output Type

(Proportional - Integral - Derivative) - The controller

modulates output power by adjusting the output power percentage within
a proportional band. Power is proportionally reduced as the process
temperature gets closer to the setpoint temperature. PID control helps
reduce overshoot on start-up, enhances stability, and compensates for
process lag. The PID parameters are automatically calculated for a par-
ticular application during the autotune procedure.

Applications for PID Control:

1. Where process temperature lags exist

2. When load changes are present

3. When overshoot is prohibited

4. When very accurate control is required

Proportional Band

- the band (expressed in degrees of temperature) in

which the controller modulates its power percentage.

Temperature Lag

- The product of thermal resistance and thermal capac-

ity. Also defined as delay of the transmission of heat from the controlled
element to the sensor caused by thermal mass of the process material
and/or process container, or the distance between the control element
and the sensor.

Upper Setpoint Limit

- prohibits users from adjusting the setpoint higher

than the selected value.

Glossary

Advertising