Display Parameter Selection

Damping

Low

Normal

High

Autotune

Damping Menu

Note: The damping parameter specifies how aggressively the
controller performs its autotuning. The “Normal” setting is a
compromise between the fast recovery and overshoot. The
“Low” setting provides faster recovery, but with the possibil-
ity of overshoot; the “High” setting a slower recovery, but with
minimum or no overshoot.

Recipe (Ramp/

Soak) Menu

Single Setpoint Ramp Time

This selection will cause the controller to ‘ramp’ the

process from the starting point (current process value)

to the setpoint in the time specified. This ramp will take

place at startup when selected from the Ramp/Soak menu.

The setpoint must be at least ±0.2% of sensor span for the

ramp to be employed.

Multi-Step Ramp

This selection will enable the programming of a recipe (make

all ramp/soak recipe variables visible). Recipes can be resumed

on startup if interrupted by a power failure or initiated, held, and

terminated from the front panel via the Mode Menu or with the

logic input option (initiate and held/resumed only).

Holdback Band

Specifies the maximum number of degrees above or below

setpoint that the process can be for the segment timer to keep

going. The timer will hold while the process settles back into the

band and then continue. If this feature is not desired, this param-

eter should be set to

which will disable it.

Termination State

This parameter determines what the control will do at the

completion of a recipe. Last Setpoint refers to the last

temperature specified in the ramp/soak recipe. Default

Setpoint refers to the standard setpoint which was in effect prior

to recipe initiation.

Recycle Number

Specifies the number of times after the first time that the recipe

is run before the program terminates.