Autotuning – Athena Technologies 16C User Manual

Page 30

Advertising
background image

26

27

Autotuning

To place the controller in Autotune mode:
1) Configure the controller by following the directions for

Initial Setup Sequence through Step 3 on page 7. Set

damping parameter. (See page 22.)

2) If the controller is not already in Standby mode, place it

in Standby now as follows. Press and hold the

Mode/Enter

key for three seconds. Display will indicate

your current operating mode. Press the Raise

key or

Lower key to select Standby. Press Mode key again

and the display will alternate between

and the pro-

cess value. This will deactivate all outputs.

3) If Setpoint Value has not been entered, adjust setpoint

now by using the Raise or Lower key to set the desired

setpoint.

4) Wait for process to stabilize before proceeding, e.g., in the

case of a heating and cooling process, return to ambient

temperature.

5) Initiate Autotuning. Press and hold the Mode/Enter key

again for three seconds, then press the Raise or Lower

key repeatedly until

appears. Finally, press the

Mode/Enter key again. The display will alternately indicate

and process value as the controller “learns” the

proper proportional band, derivative, and integral values

for the process. If unacceptable overshoot occurs on

restart, shut down the process and increase the damping

setting. If sluggish response is observed, shut down the

process and decrease the damping setting.

In order for the controller

to autotune properly, the

setpoint value must be at

least 1% of span above or

below the initial process

value. Make sure that

the Setpoint Target Time

parameter is set to OFF.

Tuning accuracy increas-

es as the spread between

ambient and setpoint

value increases.
Tuning should be

performed with system

in equilibrium (no latent

energy remaining).