29

Error Codes

If an error code cannot

be cleared by using

the actions provided,

contact factory.

Display Problem Actions

Open Sensor Check sensor,

wiring, and Input.

Reversed Sensor Check the type

selection in
the Input menu,
and check sensor
polarity.

Loop Break Correct problem

and reset controller.

Checksum Error Press any key
RAM Error to perform a
Defaults Loaded soft reset and
EEPROM Write Failure reinitialize

controller.

Power Fail Resume No further resume

Feature Disabled actions available.

Plus other Unexpected or Reset

2-Digit Invalid Interrupt controllers
Code

Autotune Errors
If a tune error condition occurs, the upper display will toggle

between

and a numeric error code for three seconds before

the tune process terminates. The controller will then automatically

go into Standby mode when a tuning error occurs. Possible error

codes are:

02 = No PID Device Configured

03 = Incorrect Output Action

05 = Insufficient Setpoint-Process Value Deviation

08 = Invalid Tune Results

09 = Tune Timeout

Ramp/Soak Errors
Possible error codes are:

02 = Recipe Empty (i.e. no non-zero ramp times)

05 = Insufficient Setpoint-Process Value Deviation