Appendix 11, Wiring diagram, Appendix 11 wiring diagram – Vaisala HMP230 User Manual

Page 162: Hmp230pw

Advertising
background image

APPENDIX 11

WIRING DIAGRAM

D igital cur-
rent loo p

In automation system
the galvanically isolated inputs
are recommended for current signals

Main board HMP230 and HMP260

To control system

Supply voltage 24 VDC
max. HMP230 series 100 mA
(with re-gaining 170 mA)
HMP260 series 120 mA

Note ! The cable shield has to be connected to the cable bushing for full EMC protection.

(To control system)

X2

1

2
3

4

1

2

3

1
2

4

Channel1+
Channel1-
Channel2+
Channel2-

RX
GND
TX
NC

-

+

Serial
connections
See manual for
details!

Humidity and
temperature outputs
current/voltage
Max. load for
mA outputs 500 ohm

X6

X1

X1

X2

N
L

+

-

X2

1 2 3 4

4

3

2

1

2 1

X1

X6

Location of main board terminals

X15

Output voltage 24 VDC

-

+

L

N

Supply voltage 115/230 VAC

HMP230PW

optional power supply
module (230/115 VAC)

HMP230PW

Fuse T160 mA

Jumper selections in
connector X15

Current 0...20 mA/4...20 mA

Ch

1

Ch2 Ch1

Ch

2

Ch

1

Ch2 Ch1

Ch

2

Ch

1

Ch2 Ch1

Ch

2

Voltage 0...1 V

See manual for details!

X1

X2

Voltage 0...5 V/0...10 V

+RX
-RX
+TX
-TX

TX

RX

RS 232C

RS 485/422

HI

LO

LO
HI

Note.
the output settings must
be also programmed

Security lock jumper

spare
jumpers

Note. HMP230PW module cannot be
used with HMP260 transmitters.

(HMP230: for 24 VAC,
see the Operating Manual)

/ ~

Advertising