Q:

How do I configure a firewall for viewLinc?

A:

viewLinc will have exceptions added in the Domain and Private

networks. Exceptions will not be added to Public networks. If this is
required, they must be added manually. Please contact Vaisala
Technical Support if you require assistance.

Setting Up Devices

Q:

My network uses a combination of Vaisala Veriteq

Devices, 300 Series and HMT140 Wi-Fi Data Loggers. How
can I add them quickly?

A:

To add multiple Transmitters or a combination of Devices and

Transmitters at one time, create a .txt definitions file with one
Device or Transmitter defined per line. Add fields to identify the
Device class and Device properties (separating each field with a tab).

To set vcom type Devices (Vaisala Veriteq Devices), define the COM
port number to which your Device is connected. For example:

vcom com_port=101

vcom com_port=102

vcom com_port=103

To set HMT330 type Devices (300 Series Transmitters), define the
following:

sample_rate = the internal sample rate of the Device

timeout = the timeout for communication events

connection = the type of connection, COM port or TCP

com_port = a COM port number to which your Device is con-
nected (values for COM port connections are user-defined)

serialno = the serial number of your Device

udp_port = UDP port number (i.e. for HMT140 Devices)

ip_port = the TCP port (values for TCP connections, ip_
address and ip_port, are user-defined)