Threshold templates, Apply templates to multiple locations, Save time by setting up – Vaisala viewLinc 4.3 User Manual

Page 64

Advertising
background image

Templates

56

4

|

4

M211679EN-A

1

From the viewLinc desktop, choose Options | System Con-
figuration | Templates |

 Alarm Templates

, select the Alarm

template you want to modify.

2

Make the required changes as outlined in steps 3 to 8 starting
on page 52.

3

Select Options |

Save

.

Threshold Templates

Threshold settings are assigned to Locations, to define the conditions
that trigger alarms. For example:

Greater than 23.00 C for more than 1 minute, or,

Less than 37.76 RH for more than 15 minutes

Threshold settings can be applied with or without templates, but a
Threshold template makes it easy to apply similar parameters to
several Locations, with single or multiple-threshold settings.

Users with can create a new Threshold template, or simply modify
one of the two default templates, High Temp and Low Temp.

Note: If threshold settings are applied to a Location, and con-

ditions exceed these settings, the Default Threshold Alarm
Template is automatically activated. To learn about Alarm
Template settings, see “Alarm Templates” on page 51.

Alarm settings can indicate whether the alarm is a mild concern
(indicated with a yellow bar, perhaps when conditions are nearing
Threshold) or an extreme concern (indicated with a red bar, when a
condition exceeds Threshold).

For

example, you could set a yellow alarm to trigger first,

automatically

sending an Email to someone who needs to know

within

a few minutes of the minor condition alert. For a red alarm,

you

could set the alarm condition to a longer time (15 minutes out of

threshold)

and send the Email to a lab manager, or a distribution list

of

people who need to be notified to take action.