Multi-threshold template – Vaisala viewLinc 4.3 User Manual

Page 66

Advertising
background image

Templates

58

4

|

4

M211679EN-A

5

To define a custom (Private) Alarm template, or modify existing
Alarm Template settings, complete the fields in the General
Parameters, Notifications, and Comments tabs.

Note: You require Manage Alarm Templates Right to modify

existing Alarm Templates. For more information, see
“Alarm Templates” on page 52.

6

When you finish creating your Threshold template, click

Options |

 Save

.

To apply the Threshold template to a Location, see “Setting Up
Location Thresholds” on page 78.

Multi-threshold Template

A multi-threshold template can have up to five threshold settings.

To create a multi-threshold template:

1

From the viewLinc desktop, select Options | System Con-
figuration | Templates |

 Threshold Templates

.

2

In the Threshold Templates window, click

Options

|

 Add

Multi-Threshold Template

.

3

Double-click anywhere in the title to change it.

4

Set the Threshold conditions:

Units

: Select the Channel’s measurement units.

Deadband

: Specify the measurement range you want

viewLinc to ignore (this range accommodates minor fluc-
tuations which you do not want to trigger an alarm).

Type

: Identify the threshold as a High limit (High or

HighHigh), or Low limit (Low or LowLow), or, indicate
the rate of change in units (ROC Units).

Value:

Enter the threshold limit.