Campbell Scientific CR5000 Measurement and Control Module User Manual

Page 130

Advertising
background image

Section 7. Measurement Instructions

7-4

TCSE (Dest, Reps, Range, SEChan, TCType, TRef, MeasOfs, SettlingTime,

Integ, Mult, Offset)

S.E. Chanel

Ground

Thermocouple

This instruction measures a thermocouple with a single-ended voltage
measurement and calculates the thermocouple temperature (

°C) for the

thermocouple type selected. The instruction adds the measured voltage to the
voltage calculated for the reference temperature relative to 0

° C, and converts

the combined voltage to temperature in

°C.

Voltage and Thermocouple Parameters

Parameter

& Data Type

Enter

Dest

Variable

or Array

The Variable in which to store the results of the instruction. When Reps are used the
results are stored in an array with the variable name. An array must be dimensioned to
have elements for all the Reps.

Reps

Constant

The number of repetitions for the measurement or instruction.

Range

Constant

Alpha
Code

Numeric
Code

Voltage
Range

mV5000 0

± 5000 mV

mV1000 1

± 1000 mV

mV200 2

± 200 mV

mV50 3

± 50 mV

mV20 4

± 20 mV

AutoRange 5

mV20 - mV5000 Selects range (Sect. 3.1)

mV200C

mV50C
mV20C

20
30
40

± 200 mV

± 50 mV
± 20 mV

The mV200C, mV50C, and mV20C
ranges pull the channel into common
mode range and check for open input

DiffChan

Constant

The differential channel number on which to make the first measurement. When Reps are
used, subsequent measurements will be automatically made on the following channels. If
the channel is entered as a negative number, all reps occur on that channel.

SEChan

Constant

The single-ended channel number on which to make the first measurement. When Reps
are used, subsequent measurements will be automatically made on the following channels.
If the channel is entered as a negative number, all reps occur on that channel.

TCType

Alpha
Code

Numeric
Code

Thermocouple Type

Constant

TypeT

0 Copper

Constantan

TypeE

1 Chromel

Constantan

TypeK

2 Chromel

Alumel

TypeJ

3 Iron

Constantan

TypeB

4 Platinum

Rhodium

TypeR

5 Platinum

Rhodium

TypeS

6 Platinum

Rhodium

TRef

Variable

The name of the variable that is the reference temperature for the thermocouple
measurements.

Advertising