7-26

SW12

The SW12 instruction is used to set a Switched 12 volt supply high or low.

Syntax
SW12( State )

Remarks
The datalogger has a switched 12 volt output with two terminals. This switched
12 volts is used to provide a continuous 12 volt supply to external peripherals.
At room temperature the switched 12 volt supply can source 900 mA between
the SW-12 terminal and Ground. The State parameter indicates whether the
switched 12 volts is High (non-zero) or low (0).

The SW-12 supply is unregulated and can supply up to 900 mA
at 20C and up to 630 mA at 50C. A resettable polymeric fuse
protects against over-current. Reset is accomplished by removing
the load or turning off the SW-12 for several seconds.

SW12 Example
This example sets the switched 12 volt supply high at the beginning of each
scan, and low at the end of the program.

Const RATE = 500

'Scan interval number

Const RUNITS = 1

'Scan interval units (mSecs)

Const TBLINT1 = 200

'Table 1 interval number

Const UNITS1 = 1

'Table 1 interval units (mSecs)

Dim Tblk1( 1 )

'Block #1 dimensioned source

Dim Tref

'Declare reference temperature variable

Public Flag( 8 )

'Flag dimension


DataTable( TEST, Flag( 1 ), 1000 ) 'Trigger, buffer of 1000 Records
DataInterval( 0, TBLINT1, UNITS1, 100 ) '200 mSecs, 100 lapses

Average( 1, Tblk1(), FP2, 0 ) 'Reps,Source,Res,Disable

EndTable

'End of table TEST


BeginProg

'Program begins here

Scan( RATE, RUNITS, 1, 0 )

'Scan 500 (mSecs), no fast buffer

SW12( 1 )

'Set SW12 high

PanelTemp( Tref., Integ )

'PanelTemp

TCDiff( Tblk1(), 1, 1, 1, 1, Tref, 0, 20, 40, 1.8, 32 )

CallTable

TEST

'Run Table TEST

SW12 ( 0 )

'Set SW12 log

Next Scan

'Loop up for the next scan

EndProg

'Program ends here

NOTE