Section 7. Measurement Instructions

7-14

Parameter
& Data Type

Enter

CAOChan

The CAO channel to set.

Constant

Alpha Numeric Description

CAO1

1

CAO channel 1

CAO2

2

CAO channel 2

CAOmV

Constant or
Variable

The voltage, in millivolts, to apply to the CAO Channel. The allowable range is

±5000

mV. The voltage can be constant or a variable can be used to vary the analog output in
response to time or measurements.

Boost

Sets the current that the CAO can sink (The CAO can always source up to 15 mA.)

Constant

Alpha Code

Value

Result

False

0

Boost off: Maximum current sink 5 mA

True

≠0

Boost Enabled: Maximum current sink 15 mA

FastUpdate

Shortens the execution time of the instruction and the settling time for the excitation.

Alpha Code

Value

Result

False

0

Settle 10 time constants (~2.6 ms)

True

≠0

Settle 1 time constant (~300

µs)

ExciteI (IxChan, IxuA, XDelay)

This instruction sets the specified current excitation channel to the current
specified.

Parameter
& Data Type

Enter

IxChan

Enter the current excitation channel number to use to excite the first measurement.

Constant

Alpha
Code

Code/
Channel

Result

IX1 1

Current Excitation Channels (IxChan)

IX2 2

IX3 3

IX4 4

ExuA

Constant

The excitation current in microamps. The allowable range is ±2500 µA.

XDelay

Specifies the length of time the current channel is enabled, after which, the channel is set
low and the datalogger moves on to the next instruction. If XDelay is set to 0, the
excitation will be on until the end of the program scan or until another instruction sets an
excitation voltage, CAO, or current channel.

ExciteV (ExChan, ExmV, XDelay)

This instruction sets the specified switched voltage excitation channel to the
voltage specified. The XDelay parameter is used to specify the length of time
the excitation channel is enabled, after which, the channel is set low and the
datalogger moves on to the next instruction. If the SettlingTime is set to 0, the
excitation channel will be enabled and the voltage will be held until the end of
the program scan or until another instruction sets an excitation voltage, CAO,
or current channel.