Portset (port, state) – Campbell Scientific CR5000 Measurement and Control Module User Manual

Page 148

Advertising
background image

Section 7. Measurement Instructions

7-22

Parameter
& Data Type

Enter

Dest
Variable

The variable in which to store the result of the instruction. A 1 is stored if the port is high;
0 is stored if the port is low.

Port
Constant

The control port number (1-8) for which the status should be obtained.

PortGet Example

This example uses PortGet to read the status of port 1 at the beginning of each
scan.

Const RATE = 500

'Scan interval number

Const RUNITS = 1

'Scan interval units (mSecs)

Const TBLINT1 = 200

'Table 1 interval number

Const UNITS1 = 1

'Table 1 interval units (mSecs)

Dim Tblk1( 1 ),PortStatus

'Block #1 dimensioned source

Dim Tref

'Declare reference temperature variable

Public Flag( 8 )

'Flag dimension


DataTable( TEST, Flag( 1 ), 1000 ) 'Trigger, buffer of 1000 Records

DataInterval( 0, TBLINT1, UNITS1, 100 )

'200 mSecs, 100 lapses

Average( 1, Tblk1(), FP2, 0 ) 'Reps,Source,Res,Disable

Sample ( 1, PortStatus, FP2 ) 'Reps,Source,Res,Disable

EndTable

'End of table TEST


BeginProg

'Program begins here


Scan( RATE, RUNITS, 3, 0 ) 'Scan 500 (mSecs)

PortGet( PortStatus, 1)

'Set port 1 high

PanelTemp( Tref. Integ ) 'PanelTemp

TCDiff( Tblk1(), 1, 1, 1, 1, Tref, 0, 20, 40, 1.8, 32 )

CallTable

TEST

'Run Table TEST

Next

Scan

'Loop up for the next scan

EndProg

'Program ends here

PortSet (Port, State)

This Instruction will set the specified port high or low.

Parameter
& Data Type

Enter

Port

Constant,
Variable, or
Expression

The number of the port (1-8) to set with the instruction.

State

The state (high or low) to set the port to.

Constant,

Code Value State

Variable, or

True 0

Low

Expression

False

≠ 0

High