Section 9. Program Control Instructions

9-13

instruction. The Attribute codes are actually a bit field.
The codes are as follows:

Bit

Decimal

Description

bit 1

2

Run on power up

bit 2

4

Run now

RunDLDFile Example

The statement below uses RunDLDFile to run TEMPS.DLD, which is stored
on the datalogger's CPU, when Flag(2) becomes high.

If Flag(2) then RunDLDFile( "CPU:TEMPS.DLD" 4 )

'4 means Run Now

Reset Table

Used to reset a data table under program control.

Syntax

ResetTable( TableName )

Remarks

ResetTable is a function that allows a running program to erase and restart a
data table. TableName is the name of the table to reset.

ResetTable Example

The example program line uses ResetTable to reset table MAIN when Flag(2)
is high.

If Flag(2) then ResetTable( MAIN )

'resets table MAIN

Scan

Used to establish the program scan rate.

Syntax
Scan(
Interval, Units, Option, Count)

...
...[Exit Scan]
...

Next Scan

The measurements, processing, and calls to output tables bracketed by the
Scan…NextScan instructions determine the sequence and timing of the
datalogger program.

The Scan instruction determines how frequently the measurements within the
Scan…NextScan structure are made, controls the buffering capabilities, and
sets the number of times to loop through the scan.