Section 7. Measurement Instructions

7-8

Parameter

& Data Type

Enter

SettlingTime

Constant

The time in microseconds to delay between setting up a measurement (switching to the
channel, setting the excitation) and making the measurement. (1 microsecond resolution)

Entry

Voltage Range

Integration

Settling Time

0

± 20 mV

Flash

200 µS (default)

0

All but ± 20 mV,

Flash

100 µS (default)

0

All

250 µS

200 µS (default)

0

All

_50Hz, _60 Hz

3 mS (default)

>=100 All

All

µS

entered

Integ

The time spent on integration in microseconds for each of the channels measured.

Constant

Entry

Integration

0, 200

Flash Conversion; 200 = 2 flash conversions 100 µS apart
and averaged

250; 500-16000

250 µS; multiples of 500: 250 µS integrations starting each
500 µS and averaged

_60Hz or 16667

16,667 µS (reject 60 Hz noise)

_50 Hz or 20000

20,000 µS (reject 50 Hz noise)

Mult, Offset

Constant,
Variable,
Array, or
Expression

A multiplier and offset by which to scale the raw results of the measurement.

7.4 Full Bridges

BrFull (Dest, Reps, Range, DiffChan, ExChan, MeasPEx, ExmV, RevEx,

RevDiff, SettlingTime, Integ, Mult, Offset)

X = result w/mult = 1, offset = 0

X

V

V

R

R

R

R

R

R

x

=

=

+

+



1000

1000

1

3

3

4

2

1

2


This Instruction applies an excitation voltage to a full bridge and makes a
differential voltage measurement of the bridge output. The resulting value
(multiplier = 1, offset = 0) is the measured voltage in millivolts divided by the
excitation voltage in volts (i.e., millivolts per volt).