Single control network, Duplicated control network, Setting selected traps (alarming) – Avaya S8710 User Manual

Page 30

Advertising
background image

Configuring the SNMP modules in the UPS

30

Installing and Configuring the Avaya S8700 or S8710 Media Server

June 2004

8

Connect one end of a CAT5 cable to the RJ45 connector on the UPS 1 SNMP module and the
other end to the next available port on the Ethernet switch for Control Network A (CNA).

9

Depending on whether a single or duplicated control network is installed (

Single control network

on page 30 or

Duplicated control network

on page 30), repeat steps 5 thru 7 for the UPS 2 SNMP

module.

10

Connect one end of a CAT5 cable to the RJ45 connector on the UPS 2 SNMP module and the
other end to the next available port on the Ethernet switch for Control Network A (CNA).

Single control network

If a single control network, use the following address and cable connection information for UPS 2:

UPS IP address / Subnet mask = 198.152.255.238 / 255.255.255.0

Default Gateway IP address = 198.152.254.202

Host Table trap receiver IP address = 198.152.254.202

Local network administrator supplied information as required for Get and Set community name
strings.

Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the Ethernet
switch for Control Network A (CNA).

Duplicated control network

If a duplicated control network, use the following addresses and cable connection information for UPS 2:

UPS IPaddress / Subnet mask = 198.152.255.239 / 255.255.255.0

Default Gateway IP address = 198.152.255.202

Host Table trap receiver IP address = 198.152.255.202

Local network administrator supplied information as required for Get and Set community name
strings.

Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the Ethernet
switch for Control Network B (CNB).

Setting selected traps (alarming)

The default is to set all traps, which may result in large log entries. Therefore, only set the following
traps. See the User’s Guide that comes with the SNMP module for the menus and commands for setting
these traps.

UPS on Battery—Indicates AC fail with pending shutdown based on battery reserve available

UPS in Bypass—Failure either Failed UPS or overload

Replace battery—Failure of periodic (28-day) battery test indicating battery needs to be replaced.