Telneting to media server, Enabling alarms, To inads via modem – Avaya S8710 User Manual

Page 65: To inads via snmp, To inads on second server

Advertising
background image

5

Completing the installation administration

Telneting to media server

Installing and Configuring the Avaya S8700 or S8710 Media Server

65

June 2004

Telneting to media server

Enabling alarms uses Linux commands through Telnet.

1

Click Start > Run to open the Run dialog box

2

Type

telnet 192.11.13.6

and press Enter.

3

Log in as

craft

or

dadmin

(if business partner).

Enabling alarms

To INADS via modem

NOTE:

These steps must be done on both media servers.

1

Type

almenable -d b

and press Enter

.

2

Type

almenable

and press Enter to verify that the alarms are enable

d.

To INADS via SNMP

NOTE:

Do these steps only if a Secure Service Gateway (SSG) is being installed.

NOTE:

These steps must be done on both media servers.

1

Type

almsnmpconf -d ipaddress -c communityname

and press Enter, where ipaddress is the

trap receiver address for the SSG device and communityname is the community string name
required by the SSG device.

2

Type

almsnmpconf

and press Enter.

Verify that the correct information was entered.

3

At the prompt, type

almenable -s y

and press Enter.

4

Type

almenable

and press Enter.

Verify that the SNMP alarm origination is enabled. If used, verify that alarm origination via
modem is still enabled.

5

Log off.

To INADS on second server

1

Connect to the second media server

2

Repeat

Telneting to media server

on page 65 through

Enabling alarms

on page 65 on the second

server.