6-14

6. PARAMETER DESCRIPTION

Example 1: To count in 1 Ml (mega-liter) steps

with flow rate span = 100 m

3

/h

Since 1 Ml = 10

3

x m

3

, k Unit/P is

set for B30/D10, and 1 is set for
B31/D11. “x10

3

m

3

” is indicated for

the totalized units in the Display
Mode.

Example 2: To count in 10 l (liter) steps with

flow rate span = 100 m

3

/h

Since 1 l = 10

-3

x m

3

, m Unit/P is

set for B30/D10, and 10 is set for
B31/D11. “x10

-2

m

3

” is indicated for

the totalized units in the Display
Mode.

Example 3: To count in 5 l (liter) steps with

flow rate span = 100 m

3

/h

Since 1 l = 10

-3

x m

3

, m Unit/P is

set for B30/D10, and 5 is set for
B31/D11. Since B31/D11 is not
0.001, 0.01, 0.1, 1, 10, 100, or
1000, there is no indication of
totalized units in the Display Mode.

• Setting of totalization scale is not possible

when specific selections have been made for
B30/D10: Total Unit, B31/D11: Total Scale,
and B23/C42: Flow Span. In such a case, a
setting alarm will be displayed, and parameters
should be changed in accordance with the
instructions given.

[B32: Pulse Unit]

Setting of the pulse units

This setting is linked with that of parameter

E10

.

This parameter selects the flow rate units to be used for
pulse output.

Item

Description

n Unit/P

u Unit/P

m Unit/P

Unit/P

k Unit/P

M Unit/P

Pulse/s

10-

9

FU

10-

6

FU

10-

3

FU

FU

10

3

FU

10

6

FU

Number of pulses to be output for one second at 100% output.

T0617.EPS

FU: Flow rate unit selected in B21/C40: Base Flow Unit.

[B33: Pulse Scale]

Setting of pulse scale

This setting is linked with that of parameter

E11

.

Pulse output is performed in individual counts in
accordance with this parameter’s setting. If 0 is
selected, it indicates that the pulse output function is
not to be used.

NOTE

If a pulse scale is specified upon ordering, this
parameter is setup before shipment; however, if
this is not the case, it will be necessary for the
appropriate value to be setup by the user.

NOTE

• By setting the pulse scale, pulse output per-

forms. The pulse scale is determined in accor-
dance with the settings of B32/E10: Pulse Unit
and B33/E11: Pulse Scale.

• If multiple ranges are being used, the flow rate

span for the smallest range becomes the
standard for the E13: Pulse Low Cut setting
value.

• Pulse output for the reverse flow rate is carried

out only when “Fwd/Rev Ranges” is selected
for F10: SO1 Function or F11: SO2 Function.

• Setting of pulse scale is not possible when

specific selections have been made for B32/
E10: Pulse Unit
, B33/E11: Pulse Scale, E12:
Pulse Width
and B23/C42: Flow Span. In
such a case, a setting alarm will be displayed,
and parameters should be changed in accor-
dance with the instructions given.

Example 1: To perform pulse output in 1 Ml

(mega-liter) steps with flow rate
span = 100 m

3

/h

Since 1 Ml = 10

3

x m

3

, M Unit/P is

set for B32/E10, and 1 is set for
B33/E11.

Example 2: To perform pulse output in 10 l

(liter) steps with flow rate span =
100 m

3

/h

Since 1 l = 10

-3

x m

3

, m Unit/P is

set for B32/E10, and 10 is set for
B33/E11.

Example 3: To perform pulse output in 5 l

(liter) steps with flow rate span =
100 m

3

/h

Since 1 l = 10

-3

x m

3

, m Unit/P is

set for B32/E10, and 5 is set for
B33/E11.

[B40: Display Select1]

Setting of the first line for

display unit

This setting is linked with that of parameter

H10

.

This parameter selects the display content of the first
line for display unit. The size of the characters which
are displayed will depend on the selections made for