IM 01E20C01-01E

6-27

6. PARAMETER DESCRIPTION

Output Example 3

The high alarm (H) is set to 80% or more of the flow
rate span; the high-high alarm (HH), to 90% or more.

Settings are:

G10: Low Alarm

= -110%

G11: High Alarm

= 80%

G12: Low Low Alarm

= -110%

G13: High High Alarm

= 90%

0

Time (t)

H

HH

SO1

SO2

HH

AL

Instantaneous flow rate

50

80

90

100

[%]

F0612.EPS

High High Alarm

High Alarm

L Alarm set to
-110% indicates
that the alarm is
disabled.

LL Alarm set to -110% indicates
that the alarm is disabled.

Select “H/L Alarm” for F10: SO1 Function
Select “HH/LL Alarm” for F11: SO2 Function
Select “Closed (On) Act” for F14: SO1/2 Active Mode
Select “Open (Off) Act” for G20: Alm Out Act Mode
Select “Yes” for G33: Alm-HH/LL

NOTE

• Although the same items can be selected using

the SO1 output terminal (selected for F10) and
the SO2 output terminal (selected for F11),
output is identical for both.

• Setting values of -110% and 110% are used to

disable corresponding functions; and accord-
ingly, status output can be customized for
specific purposes.

[G14: H/L Alarm Hys]

Setting of upper/lower alarm

value hysteresis width
This parameter sets the hysteresis width for upper and
lower alarm value, using a % value of the maximum
span.

Output Example

The hysteresis width is set to 5%.

Settings are:

G10: Low Alarm

= 30%

G11: High Alarm

= 80%

G12: Low Low Alarm

= 20%

G13: High High Alarm

= 90%

G14: H/L Alarm Hys

= 5%

0

Time (t)

H

L

HH

SO1

SO2

LL

75%

75%

35%

35%

85%

85%

25%

85%

25%

Instantaneous flow rate

20

30

50

80

90

100

[%]

F0613.EPS

HH

AL

LL

High High Alarm

High Alarm

Low Alarm

Low Low Alarm

25%

Select “H/L Alarm” for F10: SO1 Function
Select “HH/LL Alarm” for F11: SO2 Function
Select “Closed (On) Act” for F14: SO1/2 Active Mode
Select “Open (Off) Act” for G20: Alm Out Act Mode
Select “Yes” for G33: Alm-HH/LL

[G20: Alm Out Act Mode]

Setting of the active

mode for the alarm output.
This parameter selects the active mode for the alarm
output terminal.

Closed (On) Act

Open (Off) Act

When an alarm occurs, alarm output
becomes "Closed (On)."

T0631.EPS

Setting

Function

When an alarm occurs, alarm output
becomes "Open (Off)."