8. OPERATION VIA HART COMMUNICATOR

9

AXFA11 : FI-1201
Enter meter value
1.000000
1.000000

DEL

DEL

ABORT

ENTER

F4

(ENTER)

10

AXFA11 : FI-1201
Scaled output: 1.000
equal readout
device?
1 Yes
2 No

DEL

DEL

ABORT

ENTER

F4

(ENTER)

Voltmeter reading: 1.010

Enter the voltmeter’s reading of 1.010, and press ENTER
(F4)
.
(The output of the AXFA11 changes.)

Voltmeter reading: 1.000

Because the reading on the voltmeter is 1.000, select “Yes
and press ENTER (F4).
If the reading is not 1.000, select “No”.
Repeat step until the voltmeter reads 1.000 V.

‘1.01’

9

F0816-3.EPS

AXFA11 : FI-1201
Settting fld dev
output to 20mA

HELP

SAVE

ABORT

OK

11

12

Press OK (F4). The output signal of 100% is output.

Voltmeter reading: 5.210

Enter the voltmeter’s reading of 5.210, and press ENTER
(F4)
.

Voltmeter reading: 5.000

Select “Yes” and press ENTER (F4).
Returning fld dev to original output” appears.

Press OK (F4).

Press HOME (F3), and return to the “Online” menu.

AXFA11 : FI-1201
Scaled output: 5.210
equal readout
device?
1 Yes
2 No

HELP

DEL

ABORT

ENTER

13

AXFA11 : FI-1201
Enter meter value
5.000000
5.000000

HELP

DEL

ABORT

ENTER

AXFA11 : FI-1201
NOTE-Loop may be
returned to automatic
control

DEL

DEL

ABORT

OK

14

‘5.21’

F4

(ENTER)

F4

(ENTER)

F4

(OK)

F3

(HOME)

F4

(OK)

AXFA11 : FI-1201
Adjustment
1 Auto Zero Exe
2 Magflow Zero
3 D/A Trim
4 Scaled D/A trim

HELP

SAVE

HOME

ENTER

15

IMPORTANT

D/A trim should be executed only at single range mode. If D/A trim is executed at
Bi direction mode, it is possible that the current output becomes 108%.