IM 01E20C01-01E

8-12

8. OPERATION VIA HART COMMUNICATOR

F4

(ENTER)

AXFA11 : FI-1201
Enter meter value
20.000

HELP

DEL

ABORT

ENTER

8

9

AXFA11 : FI-1201
Fld dev output 20.000
mA equal to reference
meter?
1 Yes
2 No

HELP

DEL

ABORT

ENTER

F4

(ENTER)

F4

(OK)

F3

(HOME)

AXFA11 : FI-1201
NOTE-Loop may be
returned to automatic
control

DEL

DEL

ABORT

OK

10

11

AXFA11 : FI-1201
Adjustment
1 Auto Zero Exe
2 Magflow Zero
3 D/A trim
4 Scaled D/A trim

HELP

SAVE

HOME

OK

F0814-3.EPS

Ammeter reading: 19.050

Carry out the same procedures as those described in .

Ammeter reading: 20.000

Returning fld dev to original output” appears.

Press OK (F4).

Press HOME (F3), and return to the “Online” menu.

5

‘19.050’

F4

(ENTER)

F4

(OK)

AXFA11 : FI-1201
Fld dev output 4.000
mA equal to reference
meter?
1 Yes
2 No

DEL

DEL

ABORT

ENTER

6

7

AXFA11 : FI-1201
Setting fld dev
output to 20mA

HELP

DEL

ABORT

OK

Ammeter reading: 4.000

Because the reading on the ammeter is 4.000 mA, select “Yes
and press ENTER (F4).
If the reading is not 4.000 mA, select “No”.
Repeat step until the ammeter reads 4.000 mA.

Press OK (F4), and the AXFA11 outputs an output signal of
100%.