7. OPERATION VIA BRAIN TERMINAL (BT200)

7.2 AXFA11 Operation

Using a BT200

This section describes procedures for setting parameters
using a BRAIN Terminal (BT200). For more details
regarding AXFA11 functions, refer to Chapter 6:
Parameter Description; and for more details regarding
BT200 operation methods, refer to the BT200 User’s
Manual (IM IC0A11-01E).

7.2.1

BT200 Connection

Connection to a 4 to 20 mA DC signal line

The communication signal of the AXFA11 is superim-
posed onto the 4 to 20mA DC analog signals to be
transmitted.

AXFA11 terminals

BT200

BT200

BT200

BT200

Relaying
terminals

4 to 20mA
DC signal
transmission
line

Control room

Receiving
resistance:
250 to 600

Receiving
instrument

Terminal
board

F0705.EPS

I

I

Figure 7.2

Connecting the BT200

IMPORTANT

Restrictions exist with regard to the distance
over which communication is possible. (See
Chapter 11: Outline.)

IMPORTANT

If the power of flowmeter is turned off within 30
seconds after parameters have been set, these
settings will be canceled. Accordingly, please
keep the power on for at least 30 seconds after
setting parameters.

IMPORTANT

After approximately 5 minutes of inactivity, the
Auto Power-Off function will operate to turn your
BT200 off.

IMPORTANT

Be sure to set parameters as “Protect” on the
write protect function after the finish of param-
eter setting. Refer to the “Menu P: Parameter
Protection Items” and section “10.2.2” in detail.

NOTE

In case of BT200, the parameters are displayed
in English only.
Even if the language with the exception of English
is selected at B10/H30: Language, the param-
eters are displayed in English upon BT200.

7.2.2

The data update and upload/
download function of BT200

(1) The data update of BT200

When the following parameters are displayed, the mea-
sured data is updated automatically every seven seconds.

T0703.EPS

Item

A10

A20

A21

A30

A31

A32

C44

G22

G40

G41

G42

Name (BRAIN)

FLOW RATE (%)

FLOW RATE

FLW RATE (mA)

TOTAL

REV TOTAL

DIF TOTAL

VELOCITY CHK

4-20 BURNOUT

OPERATE TIME

ALM RECORD1

ALM TIME 1

Item

G43

G44

G45

G46

G47

G48

N20

N21

P20

P23

Name (BRAIN)

ALM RECORD2

ALM TIME 2

ALM RECORD3

ALM TIME 3

ALM RECORD4

ALM TIME 4

TEST SI1

TEST SI2

W PROTECT

SOFT SEAL

(2) Upload/download function of BT200

Upload function is used when the parameters of one
AXFA11 are copied to the BT200. And download
function is used when the parameters copied to the
BT200 are set to another AXFA11.
For details, refer to BT200 User’s Manual (IM
1C0A11-01E). The targeted parameters for upload and
download are following.

T0704.EPS

Item

C11/B20

C31

C32

C40/B21

C41/B22

C42/B23

C43/B24

Item

D10/B30

D11/B31

E10/B32

E11/B33

H10/B40

H11/B41

H12/B42

Name (BRAIN)

FLOW DAMPING

SIZE UNIT

NOMINAL SIZE

FLOW UNIT

TIME UNIT

FLOW SPAN

FLOW DECIMAL

Name (BRAIN)

TOTAL UNIT

TOTAL SCALE

PULSE UNIT

PULSE SCALE

DISP SELECT1

DISP SELECT2

DISP SELECT3