8. OPERATION VIA HART COMMUNICATOR

8.3.4.6

Example 3 of Other Settings: Trim Analog Output

Fine output adjustment is carried out with “D/A trim” or “Scaled D/A trim”.

D/A trim

D/A trim” is to be carried out if the calibration digital ammeter does not read exactly
4.000 mA and 20.000 mA with output signals of 0% and 100%.

Scaled D/A trim

Scaled D/A trim” is to be carried out if the output is adjusted using a voltmeter or
other types of meters with a 0% to 100% scale.

IMPORTANT

When “D/A trim” or “Scaled D/A trim” is carried out, the warning message “83:
Fix Cur Wng
” is displayed on the display unit.

Example 1: For adjustments using an ammeter (capable of measuring

±

1

µ

A.)

F0814-1.EPS

1. Device Setup

2. Diag/Service

2. Adjustment

3. D/A trim

AXFA11 : FI-1201
Adjustment
1 Auto Zero Exe
2 Magflow Zero
3 D/A trim
4 Scaled D/A trim

HELP

SAVE

HOME

ENTER

1

2

Select “D/A trim”.

Press OK (F4).

Connect an ammeter (capable of measuring

±

1

µ

A), and press

OK (F4).

Press OK (F4), and the AXFA11 outputs an output signal of
0%.

Ammeter reading: 4.115

Enter the ammeter’s reading of 4.115, and press ENTER (F4).
(The output of the AXFA11 changes.)

AXFA11 : FI-1201
Connect reference
meter

HELP

SEND

ABORT

OK

3

Open the “Output trim” display:

AXFA11 : FI-1201
WARN-Loop should be
removed from
automatic control

DEL

DEL

ABORT

OK

AXFA11 : FI-1201
Setting fld dev
output to 4mA

DEL

DEL

ABORT

OK

4

F4

5

(ENTER)

‘4.115’

AXFA11 : FI-1201
Enter meter value
4.0000

HELP

DEL

ABORT

ENTER

F4

(OK)

F4

(OK)

F4

(OK)

F0814-2.EPS