8. OPERATION VIA HART COMMUNICATOR

8.2.2

Display

The HART Communicator automatically searches for the AXFA11 on the 4 to 20 mA loop
when it is turned on. When the HART Communicator is connected to the AXFA11, it
displays the “Online” menu as shown below.
(If AXFA11 is not found, the communicator displays the message “No Device Found.
Press OK....” Press the OK ‘F4’ function key and the main menu appears. Please retry after
confirming the connection with the AXFA11.)

Manufacturer’s Field Device
Type Code

Tag (8 Characters)

<1>

<2>

<3>

<4>

<5>

Function keys

appears when the voltage

level of the battery is low

The arrow mark corresponding
to the pressed key appears.

Inverse video bar

AXFA11 :
Online
1 Device Setup
2 PV 0.0m

3

/h

3 PV AO 4.000 mA
4 PV Span 1176.5m

3

/h

SAVE

F0805.EPS

Figure 8.2.2

Display

<1>

appears and flashes during communication between the HART Communicator

and the AXFA11. In Burst Mode*,

appears.

<2> The current display menu title appears.

<3> Each item in menu <2> appears.

<4>

and/or

appear when the items are scrolled out of the display.

<5> On any given menu, the label appearing above a function key indicates the function

of that key for the current menu.

* Refer to “8.3.4.7 Burst Mode”.

8.2.3

Calling Up Menu Addresses

The 8.3.5 Menu Tree shows the configuration of the “Online” menu which is needed for
operation with the HART Communicator. The desired item can be displayed with ease by
understanding the menu configuration.

When the HART Commnicator is connected to the AXFA11, the “Online” menu will be
displayed after the power is turned on (see figure 8.2.2). Open the desired item as follows:

Key Operation

There are two ways of selecting the desired menu item.

1. Use the

or

key to select the desired item, and then press the

key.

2. Press the number key displayed for the desired item.

• To return to the previous display, press the

key, EXIT (F4), ESC (F3) or ABORT

(F3).

NOTE

Setting parameters on the display unit of the AXFA11 is not possible during
HART Communication.