APC AXFA11G User Manual

Page 89

Advertising
background image

IM 01E20C01-01E

8-15

8. OPERATION VIA HART COMMUNICATOR

8.3.4.7

Example 4 of Other Settings: Burst Mode

The AXFA11 continuously sends its stored data when the “Burst mode” is set to “On”.
Any one of instantaneous flow rate, output in %, totalization values or current output can
be selected and sent. The data is sent intermittently as a digital signal when the AXFA11 is
set in the “Burst mode.

Setting of Burst Mode

1. Device Setup

4. Detailed Setup

5. HART Output

4. Burst option

AXFA11 : FI-1100
Burst option
********
PV
% range/current
Process vars/crnt

HELP

DEL

ESC

ENTER

Select the type of data to be sent.
• Instantaneous flow rate (PV)
• Output in % and current output (% range/current)
• Instantaneous flow rate, totalization value* and current

output (Process vars/crnt)

* “Totl”, “Reverse Totl” or “Dif Totl”

Open the “Burst option” display:

5. HART Output

3. Burst mode

AXFA11 : FI-1100
Burst mode
Off
Off
On

DEL

DEL

ESC

ENTER

1

F4

2

Select “On” and press ENTER (F4).

Press SEND (F2).

(ENTER)

F2

(SEND)

Call up “Burst mode” display.

AXFA11 : FI-1100
HART Output
1 Poll addr 0
2 Num req preams 5
3 Burst mode On
4 Burst option PV

HELP

SEND

HOME

ENTER

F4

(ENTER)

F2

(SEND)

F0817.EPS

Exiting Burst Mode

Open the “Burst mode” display, and select “Off”.

8.3.4.8

Example 5 of Other Settings: Multidrop Mode

Field devices in “Multidrop Mode” refers to the connection of several field devices on a
single communication line. Up to 15 field devices can be connected when set to the
multidrop mode. To activate multidrop communication, the field device address must be
changed to a number from 1 to 15. This change deactivates the 4 to 20 mA output and
changes it to 4 mA.

Setting of Multidrop Mode

1. Device Setup

4. Detailed Setup

5. HART Output

1. Poll addr

AXFA11 : FI-1100
Poll addr
0
0

HELP

DEL

ESC

ENTER

Set the polling address (a number from 1 to 15) and press
ENTER (F4).
Then, press SEND (F2) to send the data.

Open the “Poll addr” display:

F4

(ENTER)

‘1’

F2

(SEND)

F0818.EPS