selected, a setting alarm will be displayed. The
setting should be returned to “Standard DF” in
such a case.

•When dual frequency excitation mode is

changed, perform zero adjustment. For details
on zero adjustment, refer to chapter 9.

[C21: Low MF]

Setting of the low-frequency meter

factor
This parameter sets the low-frequency meter factor for
standard dual frequency excitation.
This parameter is also used for pulsed DC excitation in
which AXFA11 is combined with a remote flowtube
the size of 500 mm (20 in.) or larger.

[C22: High MF]

Setting of the high-frequency meter

factor
This parameter sets the high-frequency meter factor for
standard dual frequency excitation.
If AXFA11 combined with a remote flowtube the size
of 500 mm or larger, high-frequency meter factor need
not be set.

NOTE

Meter Factor Settings

Meter factors of flowtube

Flowtube data plate

Converter data plate

F0601.EPS

(1) Confirm that the serial number indicated by

COMB.NO. on the AXFA11 converter’s data
plate corresponds with the AXF Remote
Flowtube’s serial number.

(2) Set the values that are marked in the

METER FACTOR fields on the data plate for
the Remote Flowtube.

(3) The meter factors are crucial in ensuring that

the electromotive force is correctly in propor-
tion to the flow velocity and are determined
at the manufacturing plant by actual-flow
calibration.

[C23: Low MF (EDF)]

Setting of the low-frequency

meter factor for EDF
This parameter sets the low-frequency meter factor as
required when Enhanced DF (i.e., enhanced dual
frequency excitation) is selected. If “Standard DF” has
been selected for

C20: Measure Mode

, neither

C23:

Low MF (EDF)

nor

C24: High MF (EDF)

is

displayed, and if “Enhanced DF” is selected, the four
parameters from

C21

to

C24

will be displayed.

[C24: High MF (EDF)]

Setting of the high-frequency

meter factor for EDF
This parameter sets the high-frequency meter factor as
required when Enhanced DF (i.e., enhanced dual
frequency excitation) is selected.

[C30: Select Flow Tube]

Setting of the flowtube’s

model
This parameter sets the models of flowtube. When
combining this product with an AXF Remote
Flowtube, “ADMAG AXF” should be selected.

[C31: Nominal Size Unit]

Setting of the nominal

size units
This parameter selects the units used for setting of the
nominal size.

[C32: Nominal Size]

Setting of the nominal size

This parameter sets the nominal size of flowtube.

[C40: Base Flow Unit]

Selection of flow units for

the flow rate span

Refer to the description of parameter

B21

.

[C41: Base Time Unit]

Selection of time units for

the flow rate span

Refer to the description of parameter

B22

.

[C42: Flow Span]

Setting of the flow rate span

Refer to the description of parameter

B23

.

[C43: Flow Decimal Pnt]

Setting of the decimal

point position for the instantaneous flow rate

Refer to the description of parameter

B24

.

[C44: Velocity Check]

Display of the flow rate span

velocity
This parameter displays the flow rate span for the
maximum range in m/s units.