11. Installation

Instruction

11.1 Select the Best Location

11.1.1 Indoor

Unit

š Do not install the unit in excessive oil fume area

such as kitchen, workshop and etc.

š There should not be any heat source or steam

near the unit.

š There should not be any obstacles blocking the air

circulation.

š A place where air circulation in the room is good.

š A place where drainage can be easily done.

š A place where noise prevention is taken into

consideration.

š Do not install the unit near the door way.

š Ensure the spaces indicated by arrows from the

wall, ceiling, fence or other obstacles.

š Mount with the lowest moving parts at least 8ft

(2.4 m) above floor or grade level.

11.1.2 Outdoor

Unit

š If an awning is built over the unit to prevent direct

sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.

š There should not be any animal or plant which

could be affected by hot air discharged.

š Keep the spaces indicated by arrows from wall,

ceiling, fence or other obstacles.

š Do not place any obstacles which may cause a

short circuit of the discharged air.

š If piping length is over the [piping length for

additional gas], additional refrigerant should be
added as shown in the table.

š Recommended installation height for outdoor unit

should be above the seasonal snow level.


Example: For XE9PKUA
If the unit is installed at 32.8 ft (10 m) distance, the
quantity of additional refrigerant should be 1.64 oz (50
g) .... (32.8 - 24.6) ft x 0.2 oz/ft = 1.64 oz. ((10-7.5) m
x 20 g/m = 50 g)








11.1.3 Indoor/Outdoor Unit Installation