13. Protection

Control

13.1 Protection Control For All Operations

13.1.1 Restart

Control

(Time Delay Safety Control)

š The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on

again by pressing OFF/ON button at remote control within this period.

š This control is not applicable if the power supply is cut off and on again.

š This phenomenon is to balance the pressure inside the refrigerant cycle.

13.1.2 Total Running Current

1 When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor

operation will be decreased.

2 If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3 However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for

3 minutes.

Model XE9PKUA

XE12PKUA

Operation Mode

X (A)

Y (A)

X (A)

Y (A)

Cooling / Soft Dry (A)

6.48

15.00

7.70

15.00

Cooling / Soft Dry (B)

6.48

15.00

7.70

15.00

Heating 7.48

15.00

9.20

15.00

Cooling / Soft Dry (C)

6.48

15.00

7.70

15.00

4 The first 30 minutes of cooling operation, (A) will be applied.

13.1.3 IPM (Power transistor) Prevention Control

š Overheating Prevention Control

1 When the IPM temperature rises to 248°F (120°C), compressor operation will stop immediately.
2 Compressor operation restarts after 3 minutes the temperature decreases to 230°F (110°C).
3 If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).

š DC Peak Current Control

1 When electric current to IPM exceeds set value of 16.0 ±2.0A, the compressor will stop operate. Then,

operation will restart after 3 minutes.

2 If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will

restart after 1 minute.

3 If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after

1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer
LED will be blinking (“F99” is indicated).