15.3 Error Codes Table

Diagnosis

display

Abnormality /

Protection control

Abnormality

Judgment

Protection

Operation

Problem Check

location

H00

No memory of failure

Normal operation

H11

Indoor/outdoor
abnormal
communication

After operation for
1 minute

Indoor fan only
operation can
start by entering
into force cooling
operation

Indoor/outdoor
communication not
establish

š Indoor/outdoor wire terminal

š Indoor/outdoor PCB

š Indoor/outdoor connection wire

H12

Indoor unit capacity
unmatched

90s after power
supply

Total indoor capability
more than maximum limit
or less than minimum limit,
or number of indoor unit
less than two

š Indoor/outdoor connection wire

š Indoor/outdoor PCB

š Specification and combination

table in catalogue

H14

Indoor intake air
temperature sensor
abnormality

Continuous for 5s

Indoor intake air
temperature sensor open
or short circuit

š Indoor intake air temperature

sensor lead wire and connector

H15

Compressor
temperature sensor
abnormality

Continuous for 5s

Compressor temperature
sensor open or short circuit

š Compressor temperature

sensor lead wire and connector

H16

Outdoor current
transformer (CT)
abnormality

— —

Current transformer faulty
or compressor faulty

š Outdoor PCB faulty or

compressor faulty

H19

Indoor fan motor
mechanism lock

Continuous
happen for 7 times

Indoor fan motor lock or
feedback abnormal

š Fan motor lead wire and

connector

š Fan motor lock or block

H23

Indoor heat
exchanger
temperature sensor
abnormality

Continuous for 5s

Indoor heat exchanger
temperature sensor open
or short circuit

š Indoor heat exchanger

temperature sensor lead wire
and connector

H24

Indoor heat
exchanger
temperature sensor
2 abnormality

Continuous for 5s

Indoor heat exchanger
temperature sensor 2 open
or short circuit

š Indoor heat exchanger

temperature sensor 2 lead wire
and connector

H27

Outdoor air
temperature sensor
abnormality

Continuous for 5s

Outdoor air temperature
sensor open or short circuit

š Outdoor air temperature sensor

lead wire and connector

H28

Outdoor heat
exchanger
temperature sensor
1 abnormality

Continuous for 5s

Outdoor heat exchanger
temperature sensor 1 open
or short circuit

š Outdoor heat exchanger

temperature sensor 1 lead wire
and connector

H30

Outdoor discharge
pipe temperature
sensor abnormality

Continuous for 5s

Outdoor discharge pipe
temperature sensor open
or short circuit

š Outdoor discharge pipe

temperature sensor lead wire
and connector

H32

Outdoor heat
exchanger
temperature sensor
2 abnormality

Continuous for 5s

Outdoor heat exchanger
temperature sensor 2 open
or short circuit

š Outdoor heat exchanger

temperature sensor 2 lead wire
and connector

H33

Indoor / outdoor
misconnection
abnormality

— —

Indoor and outdoor rated
voltage different

š Indoor and outdoor units check

H36

Outdoor gas pipe
temperature sensor
abnormality

Continuous for 5s

Heating
protection
operation only

Outdoor gas pipe
temperature sensor open
or short circuit

š Outdoor gas pipe temperature

sensor lead wire and connector

H37

Outdoor liquid pipe
temperature sensor
abnormality

Continuous for 5s

Cooling
protection
operation only

Outdoor liquid pipe
temperature sensor open
or short circuit

š Outdoor liquid pipe temperature

sensor lead wire and connector

H38

Indoor/Outdoor
mismatch (brand
code)

Brand code not match

š Check indoor unit and outdoor

unit

H39

Abnormal indoor
operating unit or
standby units

3 times happen
within 40 minutes

Wrong wiring and
connecting pipe, expansion
valve abnormality, indoor
heat exchanger sensor
open circuit

š Check indoor/outdoor

connection wire and connection
pipe

š Indoor heat exchanger sensor

lead wire and connector

š Expansion valve and lead wire

and connector

H59

ECONAVI sensor
abnormality

Continuous for 25s

ECONAVI sensor open or
short circuit

š ECONAVI sensor (defective or

disconnected)

š ECONAVI PCB

H64

Outdoor high
pressure sensor
abnormality

Continuous for
1 minute

High pressure sensor open
circuit during compressor
stop

š High pressure sensor

š Lead wire and connector

H97

Outdoor fan motor
mechanism lock

2 times happen
within 30 minutes

Outdoor fan motor lock or
feedback abnormal

š Outdoor fan motor lead wire

and connector

š Fan motor lock or block