15. Troubleshooting

Guide

15.1 Refrigeration Cycle System

In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the refrigeration
cycle depends on various conditions, the standard values for them
are shown in the table on the right.







Normal Pressure and Outlet Air Temperature (Standard)

Gas Pressure

PSI

(kg/cm

2

G)

Outlet air

Temperature

°F (°C)

Cooling Mode

130.53 ~ 174.04

(9 ~ 12)

53.6 ~ 60.8

(12 ~ 16)

Heating Mode

333.58 ~ 420.60

(23 ~ 29)

96.8 ~ 113

(36 ~ 45)

*Condition: • Indoor fan speed = High

• Outdoor temperature 95°F (35°C) at the

Cooling mode and 44.6°F (7°C) at the
heating mode
• Compressor operates at rated frequency