3 outdoor fan motor operation – Panasonic CS-XE9PKUA User Manual

Page 34

Advertising
background image

34

ii. Auto Fan Speed
[Cooling, Dry]

š According to room temperature and setting temperature, indoor fan speed is determined automatically.

š When set temperature is not achieved, the indoor fan will operate according to pattern below.

š When set temperature achieved, the indoor fan speed will be fixed. When thermostat off, the fan stop periodically.

[Heating]

š According to indoor pipe temperature, automatic heating fan speed is determined as follows.

B. Feedback control

š Immediately after the fan motor started, feedback control is performed once every second.

š During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error

counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan
motor error is detected. Operation stops and cannot on back.

12.3 Outdoor Fan Motor Operation

š It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.

š During cooling operation, and outdoor ambient temperature is below 46.4°F (8°C), outdoor fan speed will be

controlled according to outdoor piping temperature as following: