15.4.17 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)

Error Code will not display (no Timer LED blinking) but store in EEPROM

Malfunction Decision Conditions

š Freeze prevention control takes place (when indoor pipe temperature is lower than 35.6°F (2°C))


Malfunction Caused

š Air short circuit at indoor unit

š Clogged indoor unit air filter

š Dust accumulation on the indoor unit heat exchanger

š 2/3 way valve closed

š Faulty indoor unit fan motor

š Refrigerant

shortage

(refrigerant leakage)

š Clogged expansion valve or strainer

š Faulty indoor pipe temperature sensor

š Faulty indoor unit PCB


Troubleshooting