11.3.3 Evacuation of the Equipment

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND
PIPES in the following procedure.

1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way

valve.

2 Connect the micron gauge between vacuum pump and service port of outdoor units.
3 Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and to pull

down to a value of 500 microns.

4 To make sure micron gauge a value 500 microns and close the low side valve of the charging set and turn off

the vacuum pump.

5 Disconnect the vacuum pump house from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 13.3 Ibf.ft (18 N•m) with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “Open”

using a hexagonal wrench (5/32" (4 mm)).

8 Mount valve caps onto the 2-way valve and the 3-way valve.

o

Be sure to check for gas leakage.


š If micron gauge value does not descend 500 microns, take the following measures:

-

If the leak stops when the piping connections are tightened further, continue working from step e.

-

If the leak does not stop when the connections are retightened, repair location of leak.

-

Do not release refrigerant during piping work for installation and reinstallation.

-

Be careful with the liquid refrigerant, it may cause frostbite.

11.3.4 Connect the Cable to the Outdoor Unit

1 Remove control board cover (Resin and

Metal).

2 Remove particular plate.
3 Remove

plugs.

4 Fix the conduit connectors to the knockout

holes with lock-nuts, then secure them against
the side panel.

5 All wires pass through conduits & particular

plate’s opening hole.

6 Connecting wire between indoor unit and

outdoor unit should be UL listed or CSA
approved 4 conductor wires minimum AWG16
in accordance with local electric codes.

7 Wire connection to the power supply

(208/230V 60Hz) through circuit breaker.

o

Connect the UL listed or CSA approved
wires minimum AWG14 to the terminal
board, and connect the other end of the
wires to ELCB/ GFCI.

8 Connect the power supply cord and

connecting wire between indoor unit and
outdoor unit according to the diagram below.