4 compressor overheating prevention control, 6 low frequency protection control 1, 7 low frequency protection control 2 – Panasonic CS-XE9PKUA User Manual

Page 45

Advertising
background image

45

13.1.4 Compressor

Overheating Prevention Control

š Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The

changes of frequency are as below.

š If compressor discharge temperature exceeds 224.6°F (107°C), compressor will be stopped, occurs 4 times per

20 minutes, timer LED will be blinking. (“F97” is indicated.)

13.1.5 Low Pressure Prevention Control (Gas Leakage Detection)

š Control start conditions

o

For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A.

o

During Cooling and Soft Dry operations:

Indoor suction temperature - indoor piping temperature is below 7.2°F (4°C).

o

During Heating operations :

Indoor piping temperature - indoor suction is under 9°F (5°C).

š Control

contents

o

Compressor stops (and restart after 3 minutes).

o

If the conditions above happen 2 times within 20 minutes, the unit will:

ƒ

Stop

operation

ƒ

Timer LED blinks and “F91” indicated.

13.1.6 Low

Frequency

Protection Control 1

š When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency

will be changed to 23 Hz for 2 minutes.

13.1.7 Low

Frequency

Protection Control 2

š When all the below conditions comply, the compressor frequency will change to lower frequency.

Temperature, T, for:

Cooling/Soft Dry

Heating

Indoor intake air (°C)

T < 14 or T ≥ 30

T < 14 or T ≥ 28

Outdoor air (°C)

T < 13 or T ≥ 38

T < 4 or T ≥ 24

Indoor heat exchanger (°C)

T < 30

T ≥ 0

Temperature, T, for:

Cooling/Soft Dry

Heating

Indoor intake air (°F)

T < 57.2 or T ≥ 86.0

T < 57.2 or T ≥ 82.4

Outdoor air (°F)

T < 55.4 or T ≥ 100.4

T < 39.2 or T ≥ 75.2

Indoor heat exchanger (°F)

T < 86.0

T ≥ 32.0