17.2 Sensible Capacity Chart


š CU-XE9PKUA

208-230V Outdoor

Temperature

Indoor

wet bulb

86 °F (30 °C)

95 °F (35 °C)

104 °F (40 °C)

114.8 °F (46 °C)

TC SHC IP TC SHC IP TC SHC IP TC SHC IP

62.6°F

(17.0 °C)

2.53 1.92 0.49 2.36 1.84 0.53 2.20 1.77 0.57 2.00 1.68 0.61

66.2°F

(19.0 °C)

2.55

0.54

67.1°F

(19.5 °C)

2.78 2.01 0.50 2.60 1.93 0.54 2.41 1.86 0.58 2.20 1.77 0.63

71.6°F

(22.0 °C)

3.03 2.08 0.51 2.83 2.00 0.55 2.63 1.93 0.59 2.39 1.84 0.64


š CU-XE12PKUA

208-230V Outdoor

Temperature

Indoor

wet bulb

86 °F (30 °C)

95 °F (35 °C)

104 °F (40 °C)

114.8 °F (46 °C)

TC SHC IP TC SHC IP TC SHC IP TC SHC IP

62.6°F

(17.0 °C)

3.33 2.53 0.73 3.11 2.42 0.79 2.90 2.33 0.84 2.63 2.21 0.91

66.2°F

(19.0 °C)

3.36

0.80

67.1°F

(19.5 °C)

3.66 2.65 0.75 3.42 2.54 0.80 3.18 2.45 0.86 2.89 2.33 0.93

71.6°F

(22.0 °C)

3.99 2.74 0.76 3.73 2.64 0.82 3.47 2.55 0.87 3.15 2.43 0.94


TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
Indoor 80.6°F/66.2°F (27°C/19°C)
Outdoor 95.0°F/75.2°F (35°C/24°C)