TROUBLESHOOTING

9-9

SRM-HW/HWC 8/99

Performance

Performance Checkout

HW/HWC chassis come with a pre-charged chassis assembly. The
chassis assembly is designed in a way that the unit may be run indepen-
dently of the HWC unit. When the chassis is run on a floor or bench, the
performance measurements will be affected due to the change in static
pressures, recirculated air, excessive temperatures and equal ambient
temperatures from indoor to outdoor.

Two sets of tables are provided in this section to address these issues.
Tables 9-1 to 9-4 are to be used when the chassis is still installed in the
complete unit. Tables 9-5 and 9-6 are to be used when the chassis is run
independently outside of the unit.

Note: Pressures may vary +/– 10 psi. Temperatures may vary =/– 2-3°F.

Performance Tests (Chassis Installed in Unit)

Total

Air Vol.

(CFM)

Enter.

DB/WB

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Outdoor Air Temperature Entering Outdoor Coil

85°

95°

105°

115°

400
450
500
400

450
500
400
450
500

75°/63°

80°/67°

85°/71°

81

49

87

82

49

97

84

50

107

85

51

117

83

54

87

84

50

97

86

51

107

87

52

117

85

60

87

86

52

97

88

52

107

89

53

117

87

63

87

88

53

97

89

53

107

91

54

117

88

68

88

90

58

97

91

54

107

93

55

117

90

73

88

92

63

97

93

57

107

95

56

117

92

74

88

93

64

97

94

56

108

96

57

117

94

79

88

95

71

97

96

62

108

98

58

117

96

84

88

97

74

97

98

65

108

100

59

117

Based on a normally installed cooling chassis

TABLE 9-1

HWC122 Performance Test (Chassis Installed)

Total

Air Vol.

(CFM)

Enter.

DB/WB

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Outdoor Air Temperature Entering Outdoor Coil

85°

95°

105°

115°

550
600
650
550

600
650
550
600
650

75°/63°

80°/67°

85°/71°

80

49

96

81

48

106

84

50

114

86

51

123

82

54

96

83

50

106

86

51

114

88

52

123

84

59

96

85

52

106

88

52

114

90

54

124

86

62

98

88

53

106

90

54

115

92

55

124

87

67

98

89

58

107

91

54

116

94

56

125

99

72

98

91

62

107

93

57

116

95

56

125

91

73

99

93

64

107

95

56

116

97

58

125

93

78

99

95

70

108

97

63

117

99

59

126

95

83

99

97

74

108

99

66

117

101

60

126

Based on a normally installed cooling chassis